Maintenance unit, Sprinkler reserve box

Maintenance unit VWE

VIROTEC®-maintenance unit VWE for the use in dry pipe sprinkler systems

The VIROTEC®-maintenance unit is a draining fitting for use in dry systems. It collects the condensation water arising at the lowest point in the dry system and can be easily drained during re - gular maintenance work.

 

Operation

VWE standard:
To drain the maintenance unit the upper ball valve (2) is closed, the 1” plugs (4) removed and the lower ball valve (3) opened. After draining, seal the plugs (4) and screw in. Close the lower ball valve (4) by 45° and reopen the upper ball valve (2) by 45°.

VWE with filler neck:
To drain the maintenance unit, the upper ball valve (2) is closed, the 1” plug (4) is removed and the lower ball valve (3) is opened. After draining, seal the plug (4), screw in and close the lower ball valve (3) by 45°. Properly dispose of any water/anti-freeze mixture collected. To fill with anti-freeze mixture, keep the upper ball valve (2) closed or close it. Remove the 1/2” plug (7) and fully open the 1/2” ball valve (5). Pour in anti-freeze and seal 1/2” plug (7), screw in and re-close 1/2” ball valve (5) and the re-open the upper ball valve (2) by 45°.


Important

According to the manufacturer’s information the ball valves (2+3+5) are only frostproof in the 45° position of the wing handle! When delivered the ball valves (2+3+5) are always fully closed. To put into ser vice, all the wing handles have to be rotated into the 45° position.

Function

The VIROTEC®-VWE standard maintenance unit consists of the following parts:
  • Item 1 Pitot pipe
  • Item 2 Upper ball valve 1”
  • Item 3 Lower ball valve 1”
  • Item 4 1” plug
    The maintenance unit is supplied completely assembled.

The VIROTEC®-VWE maintenance unit with filler neck consists of the following parts:

  • Item 1 Pitot pipe
  • Item 2 Upper ball valve 1”
  • Item 3 Lower ball valve 1”
  • Item 4 1” plug
  • Item 5 1/2” ball valve
  • Item 6 VTS 2” x 1/2”
  • Item 7 1/2” plug
    The maintenance unit is supplied completely assembled.

The DN 15 filler opening can be used to fill the maintenance unit with up to 1/3 full with anti-freeze and therefore prevent freezing up. According to the manufacturer, the ball valves are only frostproof in the 45° wing handle position.

 

Technical data

  • Type: VWE Standard or VWE with filler neck
  • Surface: Zinced
  • Material: Steel tube according to DIN 2458
  • Weight: Standard – 2.4 kg with filler neck – 3.1 kg
  • Content: Approx. 0.9 litre
  • Protective rights: GbM

Approvals

VdS applicable

Wartungseinheit VWE

Sprinkler reserve box VSR 24

VIROTEC®-VSR the ideal storage system

VIROTEC® VSR 24 sprinkler reserve boxes are an ideal storage system for sprinklers, sprinkler spanners and the operating and maintenance manual. The sprinkler reserve box provides space for 24 sprinklers. It has a storage compartment in the side for sprinkler spanners, tools, etc. and a holder in the cover for the operating and maintenance manual. The integrated writing desk rounds off the storage system. VIROTEC® VSR 24 sprinkler reserve boxes are the ideal storage system in the sprinkler control centre.


Installation information

Due to the writing desk function, VIROTEC® VSR 24 sprinkler reserve boxes should be fitted at a comfortable writing height!


Function

VIROTEC® sprinkler reserve box VSR-24 combine three functions in one. Protects against dust and external influences; the sprinkler compartment (item 1) securely stores up to 24 sprinkler heads in sizes 3/8”, 1/2” and 3/4”. In addition, a side tool compartment (Item 2) of the VIROTEC® sprinkler reserve box VSR-24 provides adequate space for tools and sealing materials such as sprinkler spanners, Teflon tape, small materials, etc. The operating and maintenance manual is securely stored in the loops under the front cover. The front cover can be completely hinged upward and therefore ensures free access to all the storage compartments and the operating and maintenance manual. The practical desk function of the front cover (Item 3) is achieved by locking the hinged clamp (Item 4) in the front cover. The desk edge (Item 5) prevents the documents from slipping off. To close the box, push the hinged clamp (Item 6) upwards and then close the front cover.

 

Sprinklerreservebox VSR-24

Product range System VIROTEC®
Product range System VIROTEC®