Drop nipple, Telescope pipe, Flexarm®

Drop nipple
VIROTEC®-Drop nipple in diameters 3/4” and 1”

The VIROTEC®-drop nipple is a pipe which can be used as a riser or downpipe for directly screwing in sprinklers in fixed, stationary water systems for extinguishing fires. It is available in the pipe dimensions 3/4” and 1”, in the lengths 0.5 m and 1.0 m, with one-sided or double-sided reduction and with 3/8”, 1/2” and 3/4” threaded outlet connections.
Fallrohr

Fallrohr

Mounting instruction

  1. Determine the required component length.
  2. Shorten the VIROTEC®-drop nipple to the required length.
  3. Cut the outer thread and seal.
  4. Screw the VIROTEC®-drop nipple in the relevant fitting.
  5. Seal the sprinkler and screw into the inner thread (max. 25 Nm tightening torque).
  6. After fitting the sprinkler, visually inspect for cracks at the reducer.

 

 

Function

The VIROTEC®-drop nipple is made as a welded threaded pipe to DIN 2440. It is available in primed and zinced versions and in the standard lengths 0.5 and 1.0 m. The VIROTEC®-drop nipple is cut to the required length on building site and equipped with an outer thread. In the double-sided reduced pipe the cutting produces two drop nipples.


Technical data

  • Surface: Primed or zinced
  • Material: Pipe thread according to DIN 2440
  • Weigth:
    3/4” 1.500 mm long – 0.8 kg
    3/4” 1,000 mm long – 1.6 kg
    1” 1.500 mm long – 1.2 kg
    1” 1,000 mm long – 2.4 kg
  • Custom-made product: Alternative surface and length on inquiry



Approvals

VdS- and FM applicable

Telescope pipe VS
VIROTEC®-telescope pipe length tailor-made

The VIROTEC®-telescope pipe VS is an adjustable drop nipple for use in fixed, stationary water systems for extinguishing fires. It enables precise adjustment of the sprinkler heads to the location of a suspended ceiling in a vertical direction. The initial length can be adjusted to the installed situation by shortening the outer pipe. The longitudinal adjustment can take place after the pipe network has been completely installed. The installation time is considerably reduced

 

VIROTEC®-Telerohr

VIROTEC®-Telerohr

Mounting instruction

  1. Determine the installed length and if necessary shorten the tele pipe at the outer pipe (only VS 0.3 and VS 0.4 models). Important: Note the marking for the smallest length (160 mm).
  2. If necessary cut outer thread R1”.
  3. Seal the thread and fit the component. 4. Adjust length, adjustment made by screwing (also possible under pressure).
    Important: The adjusting pipe may only be screwed in up to the start of the outer pipe!


Function

The VIROTEC®-telescope pipe VS is made up of the following components:

  • Item 1 Outer pipe (CED-coated, black)
  • Item 2 Adjusting pipe (CED-coated, black)
  • Item 3 O-ring (silicon)

The outer pipe of the VIROTEC®-telescope pipe VS, VS 0.3 and VS 0.4 models, can be shortened to the required installed length (up to at least 160 mm) before installation. All models are ready to install with outer thread R 1”. The length is adjusted by screwing the adjusting pipe and outer pipe together. This is also possible under pressure. The seal seals off the gap between the two pipes.

Technical data

  • Surface: CED-coated (black)
  • Weigth:
    Type 0.0: approx. 0.31 kg
    Type 0.1: approx. 0.35 kg
    Type 0.2: approx. 0.50 kg
    Type 0.3: approx. 0.70 kg
    Type 0.4: approx. 0.90 kg
  • Thread: Pipe thread R1”, Rp 3/8”, 1/2” according DIN 2999 (ISO 7-1)
  • Working temperature: - 20 °C to 110 °C
  • Working pressure: PN 25 (25 bar)

 
Approvals

Zulassungen

Telescope pipe VSI

VIROTEC®-telescope pipe length tailor-made

The VIROTEC®-telescope pipe VSI is an adjustable drop nipple for use in fixed, stationary water systems for extinguishing fires. It enables precise adjustment of the sprinkler heads to the position of a suspended ceiling in a vertical direction. The initial length can be adjusted to the installed situation by lengthening the pre-fitted double nipple. The longitudinal adjustment can be carried out after the pipe network has been completely installed. The installation time is considerably reduced.

 

Telerohr VSI

Mounting instruction

  1. Determine the installed length and if necessary lengthen the tele pipe with a 1” double nipple.
  2.  If necessary seal the extension and fit the component.
  3. Adjust length; adjust by screwing (even possible under pressure).
    Important: The adjusting pipe may only be screwed in up to the start of the connecting pipe!

Function

The VIROTEC®-telescope pipe VSI is made up of the following components:

  • Item 1 Outer pipe (CED-coated, black)
  • Item 2 Adjusting pipe (CED-coated, black)
  • Item 3 O-ring (silicon)

The VSI 0.1 and VSI 0.2 models are ready to install with a 1” inner thread. They have a double nipple for the extension. The length of the double nipple depends on the respective installed situation in the suspended ceiling and is freely selectable. It cannot be shortened by sawing. The precise lengthwise adjustment is achieved by screwing the adjusting pipe and outer pipe to gether. This is also possible under pressure. The seal seals off the gap between the two pipes.

Technical data

  • Surface: CED-coated (black)
  • Weigth:
    Type 0.1: approx. 0.45 kg
    Type 0.2: approx. 0.60 kg
  • Thread: Pipe thread Rp 1”, 1/2”, 3/8” according DIN 2999 (ISO 7-1)
  • Working temperature: - 20 °C to 110 °C
  • Working pressure: PN 25 (25 bar)
  • Protective: Patent/GbM pending

 

Approvals

Zulassungen

Telescope pipe VSN

VIROTEC®-telescope pipe lenght tailor-made

The VIROTEC®-telescope pipe VSN is an adjustable drop pipe for use in fixed, stationary water systems for extinguishing fires. It enables precise adjustment of the sprinkler heads to the position of a suspended ceiling in a vertical direction. The initial length can be adjusted to the installed situation by shortening the pre-fitted double nipple. The longitudinal adjustment can be carried out after the pipe network has been completely installed. The installation time is considerably reduced.

 

Telerohr VSN

Mounting instruction

  1. Determine the installed length and if necessary shorten the tele pipe at the 1” double nipple.
  2. If necessary, cut the outer thread R1”.
  3. Seal the thread and fit the component.
  4. Adjust the length; adjust by screwing (possible even under pressure).
    Important: The adjusting pipe may only be screwed in up to the start of the outer pipe!

Function

The VIROTEC®-telescope pipe VSN is made up of the following components:

  • Item 1 Outer pipe (KTL coated, black)
  • Item 2 Adjusting pipe (KTL coated, black)
  • Item 3 O-ring (silicon)
  • Item 4 1” double nipple, 260/830 mm long (zinced)

The VSN models are ready to install with a 1” outer thread. They consist of a VIROTEC®-telescope pipe VSI 0.2 and a pre-fitted double nipple. The VIROTEC®-telescope pipe VSN can be shortened to the required installed length (up to min. 300 mm) before installation. The precise length is set by screwing the adjusting pipe and outer pipe together. This is also possible under pressure. The seal seals off the gap between the two pipes.

Technical data

  • Surface: KTL coated (black) double nipple zinced
  • Weigth:
    Type 0.5: approx. 1.30 kg
    Type 1.0: approx. 2.60 kg
  • Thread: Pipe thread Rp 3/8”, 1/2”, R1” according to DIN 2999 (ISO 7-1)
  • Working temperature: - 20 °C to 110 °C
  • Working pressure: PN 25 (25 bar)
  • Protective rights: Patent/GbM pending

Approvals

VdS und FM applicable, see section 3.4 Telescope pipe VSI.
For hydraulically calculation, the 1” double nipple (threaded pipe 1”, length 0.26/0.83 m) has to be considered.

 

Flexarm® FL 1

VIROTEC®-Flexarm® turned to the point

The VIROTEC®-Flexarm® FL 1 is a length adjustable arm over pipe for use in fixed, stationary water systems for extinguishing fires. The Flexarm® was specially designed for use in the area of suspended ceilings, where conventional working methods require a large number of adjustments. It enables fast, easy and precise horizontal adjustment to each point within the area of a ceiling panel with a grid dimension of 625 mm. The type FL 1 is intended for mounting abouve the branch line pipe.

Flexarm® FL 1

Flexarm® FL 1

Mounting instruction

  1. Seal the 1” connecting thread at the connector (Item 3).
    Important: When using liquid sealants, note the sealant instructions for use.
  2. Screw in connector (Item 3) and tight on firm with pipe wrench.
  3.  Place the Flexarm® in the required position and secure it by ligth tightening (approx 5 Nm) the setscrews (Item 5).
  4.  Subsequent adjustment is possible at any time, even when pressurised:
    – Undo setscrews (Item 5)
    – Adjust to required position
    – Tighten setscrews (Item 5)
    Important: The locking pins (Item 4) on the inside must not be loosened or twisted out as otherwise any warranty claims are cancelled.

Function

The VIROTEC®-Flexarm® consists of the following components:

  • Item 1 Connecting arm (casting, zinced)
  • Item 2 End arm (casting, zinced)
  • Item 3 Connector (casting, zinced)
  • Item 4 Locking pins (assembly fixing, inside)
  • Item 5 Setscrews (position fixing)
  • Item 6 O-ring (silicon)

The unit is adjusted by swivelling the connecting and end arm in the horizontal plane. The hinges are sealed with an O-ring (Item 6). The locking pins (Item 4) prevent the components from falling part. These locking pins cannot be dismantled (sealed in the factory). The set position is fixed by tightening the two external setscrews (Item 5). Before installation or positioning, these setscrews are only undone by approx 1/2 turn (delivered condition) and are then re-tightened. The positioning can also take place under pressure.
Important: The locking pins on the inside must not be loosened or twisted out (warranty expires).

Technical data

  • Surface: Zinced
  • Weight: 1.75 kg
  • Packaging unit: 12 pieces
  • Thread: Pipe thread R, Rp 1” according to DIN 2999 (ISO 7-1)
  • Working temperature: - 20 °C to 110 °C
  • Working pressure: PN 25 (25 bar)
  • Pressure loss: 4.8 m equipollent length of 1” steel pipe according to DIN 2440 (33.7 x 3.2 mm)
  • Protective rights: Patent/GbM

 

Zulassungen

Flexarm® FL 2
VIROTEC®-Flexarm® turned to the point

The VIROTEC®-Flexarm® FL 2 is a length adjustable arm over pipe using a combination of cast shaped pipe parts, for use in fixed, stationary water systems for extinguishing fires. The Flexarm® was specially designed for use in the area of suspended ceilings, where conventional working methods require a large number of adjustments. It enables fast, easy and precise horizontal adjustment to each point within the area of a ceiling panel with a grid dimension of 625 mm. The type FL 2 is intended for mounting below the branch line pipe.
Flexarm® FL 2

Flexarm® FL 2

Mounting instruction
  1. Seal the 1” connecting thread at the connector (Item 3).
    Important: When using liquid sealants, note the sealant instructions for use.
  2. Screw in connector (Item 3) and tight on firm with pipe wrench.
  3. Place the Flexarm® in the required position and secure it by light tightening (approx 5 Nm) the setscrews (Item 5).
  4. Subsequent adjustment is possible at any time, even when pressurised:
    – Undo setscrews (Item 5)
    – Adjust to required position
    – Tighten setscrews (Item 5)
    Important: The locking pins (Item 4) on the inside must not be loosened or twisted out as otherwise any warranty claims are cancelled.

Function

The VIROTEC®-Flexarm® consists of the following components:

  • Item 1 Connecting arm (casting, zinced)
  • Item 2 End arm (casting, zinced)
  • Item 3 Connector (casting, zinced)
  • Item 4 Locking pins (assembly fixing, inside)
  • Item 5 Setscrews (position fixing)
  • Item 6 O-ring (silicon)

The unit is adjusted by swivelling the connecting and end arm in the horizontal plane. The hinges are sealed with an O-ring (Item 6). The locking pins (Item 4) prevent the components from falling part. These locking pins cannot be dismantled (sealed in the factory). The set position is fixed by tightening the two external setscrews (Item 5). Before installation or positioning, these setscrews are only undone by approx 1/2 turn (delivered condition) and are then re-tightened. The positioning can also take place under pressure.
Important: The locking pins on the inside must not be loosened or twisted out (warranty expires).

Technical data

  • Surface: Zinced
  • Weight: 1.75 kg
  • Packaging unit: 12 pieces
  • Thread: Pipe thread R, Rp 1” according to DIN 2999 (ISO 7-1)
  • Working temperature: - 20 °C to 110 °C
  • Working pressure: PN 25 (25 bar)
  • Pressure loss: 3.9 m equipollent length of 1” steel pipe according to DIN 2440 (33.7 x 3.2 mm)
  • Protective rights: Patent/GbM


Approvals

Zulassungen

Product range System VIROTEC®
Product range System VIROTEC®